RL 140 ME – RL 260 ME
Electrical-control cabinet, scope of delivery
Automatic alternating switch with internal timer for double ring pump system, consisting of:
-
2 pcs. motor protect switches
-
Start-up button
-
Operating lamp
-
Malfunction warning lamp
-
Alternative operation with pump 1 and pump 2 with timer, duration of run adjustable for each pump
-
Time relay for bridging pressure drop
-
Transistor relay
-
Automatic breakdown switching over in case of malfunction (indication with warning light)
-
Automatic pump alternation in case of an actuating motor protect switch
-
Optional manual alternation from pump 1 to pump 2
TYPE | RL 140 ZW | RL 260 ZW | |
---|---|---|---|
MAX. FLOW | l/h | 140 | 260 |
FEEDING FLOW | l/h | 70 | 130 |
UNIT CONNECTIONS | SUCTION | 1/2” | 1/2” |
DRIVE | 1/2” | 1/2” | |
OVERPRESSURE | 1/2” | 1/2” | |
SUPPLY VOLTAGE | VOLT | 400 tri-phase | 400 tri-phase |
MOTOR POWER | KW | 0,25 | 0,37 |
C.V. | 1/3 | 1/2 | |
OVERPRESSURE VALVE OPENS AT: |
bar | 6,5 | 6,5 |
DIMENSIONS | mm | 800 x 800 x 300 | 800 x 800 x 300 |
WEIGHT | kg | 65 | 74 |