08. GPS 10 / OUF 88

Groupe de transfert monotube aspiration- OUF 88

Applications & Specific Features

  • Oil supply to appliance by gravity feed, GPS unit must be higher than appliance(s).
  • Various GPS models available with different sizes of reservoir.
  • Standard unit has 2 outlets for 2 appliances, more outlet versions available to special order.
  • Suction lift 9m vertical or 200m horizontal. See performance curves (Datasheet).
  • Oil supply installations using ‘dead leg’ pipework. GPS unit does not need external controls.
  • Anti siphon valve or ‘normally closed’ solenoid valve required at the main oil tank when oil level in tank is above GPS level.
  • Special GPS models available with greater reservoir, for acting as power generator reservoir
  • Special GPS models available with larger flow, for high output or modulating burners

Caractéristiques Techniques

PUMP TYPE Suction Solenoid Pump
LIFTING HEIGHT (MAX.) 8 m. vertical (8 mm I.D. tube)
MÁX. HORIZONTAL DISTANCE 100 m. horizontal (8 mm I.D.. tube)
OUTLET FLOW RATING (8 MM I.D. TUBE) 8 l/hr at: 8 m vertical & 25 m horizontal 15 l/hr at: 5 m vertical & 25 m horizontal
INLET CONNECTION 3/8“ F BSP
OUTLET CONNECTION 3/8“ F BSP
OVERFLOW OUTLET CONNECTION 1/2“ F BSP
POWER SUPPLY AC 230V, 50Hz
POWER CONSUMPTION 50 W
RESERVOIR TOTAL CAPACITY 3,5 Litre
DIMENSIONS (W X D X H) 240 x 125 x 300 mm
WEIGHT 3 kg
FUEL TYPE Kerosene & Diesel Oil