08. GPS 10 / OUF 88
Groupe de transfert monotube aspiration- OUF 88
Applications & Specific Features
- Oil supply to appliance by gravity feed, GPS unit must be higher than appliance(s).
- Various GPS models available with different sizes of reservoir.
- Standard unit has 2 outlets for 2 appliances, more outlet versions available to special order.
- Suction lift 9m vertical or 200m horizontal. See performance curves (Datasheet).
- Oil supply installations using ‘dead leg’ pipework. GPS unit does not need external controls.
- Anti siphon valve or ‘normally closed’ solenoid valve required at the main oil tank when oil level in tank is above GPS level.
- Special GPS models available with greater reservoir, for acting as power generator reservoir
- Special GPS models available with larger flow, for high output or modulating burners
Caractéristiques Techniques
PUMP TYPE | Suction Solenoid Pump |
---|---|
LIFTING HEIGHT (MAX.) | 8 m. vertical (8 mm I.D. tube) |
MÁX. HORIZONTAL DISTANCE | 100 m. horizontal (8 mm I.D.. tube) |
OUTLET FLOW RATING (8 MM I.D. TUBE) | 8 l/hr at: 8 m vertical & 25 m horizontal 15 l/hr at: 5 m vertical & 25 m horizontal |
INLET CONNECTION | 3/8“ F BSP |
OUTLET CONNECTION | 3/8“ F BSP |
OVERFLOW OUTLET CONNECTION | 1/2“ F BSP |
POWER SUPPLY | AC 230V, 50Hz |
POWER CONSUMPTION | 50 W |
RESERVOIR TOTAL CAPACITY | 3,5 Litre |
DIMENSIONS (W X D X H) | 240 x 125 x 300 mm |
WEIGHT | 3 kg |
FUEL TYPE | Kerosene & Diesel Oil |