RL N/GE BIO FUEL RING TRANSFER SKID
Fuel Ring Transfer Systems for feeding burners or generators (generator sets). Normal Model
Normal model: flow rates from 100 l/h up to 1,200 l/hApplications & Specific Features
- Pump for ‘Ring Main’ oil transfer systems.
- Single or multiple appliances at same height or varying height.
- Suitable for high output or modulating burners.
- For use on oil supply installations where a GP ‘dead leg’ system is not practical.
- A back pressure relief valve (overflow valve) is required to maintain adequate pressure in the ‘Ring Main’.
- Special RL units available for aggressive or heated non standard fuels.
Accessories and adaptations
- Special non –ferrous metal free versions upon request.
- Standard motor power ready for viscosities till 38mm2/s (40ºC). For other, please consult.
- IM system to stop pumps when all burners are off (optional for RL one pump).
- Free voltage relay output to control from centralised Building Management System, in kit 3, 4 or 6 signals (2-thermal, motors 1 or 2 ON, low pressure and Leak safety ON).
- GSM alarm system by SMS messages, or connection to modem.
- Adaptation of Pressure Group for high pressure, working conditions above 6,5 Kg/cm2.
- Leak collector trays with infrared detectors (standard in RL-4 and above).
- Modifications to adapt to specifically regulated environments (tropi
MODEL RL 0 RL 1 RL 2 RL 3 RL 4 RL 5 RL 6 RL 7 RL 8 RL 9 RL 10 MAX. FLOW l/h 100 260 460 900 1400 2100 3400 5300 7500 10500 12000 SUPPLY FLOW l/h 65 150 300 600 900 1450 2300 3600 4900 7000 8000 SUPPLY VOLTAGE VOLT 400* 400 400 400 400 400 400 400 400 400 400 MOTOR POWER KW 0,25 0,25 0,25 0,55 0,55 2,2 3 3 4 4 4 CV 1/3 1/3 1/3 3/4 3/4 3 4 4 5,5 5,5 5,5 MOTOR r.p.m 1400 1400 1400 1400 1400 1400 1400 1400 1400 1400 1400 CONNECTION TO THE HYDRAULIC CIRCUIT (Ø THREAD / Ø MM) SUCTION DN 20 DN 25 DN 25 DN 32 DN 32 DN 50 DN 50 DN 50 DN 40 DN 50 DN 65 DRIVE DN 20 DN 25 DN 25 DN 32 DN 32 DN 50 DN 50 DN 40 DN 40 DN 50 DN 50 OVERPRESSURE 1/2” F 3/4”F 3/4”F 1” F 1” F DN 40 DN 40 DN 40 DN 40 DN 40 DN 40 MAX. SUCTION m 5 5 5 5 5 5 5 5 5 5 5 SECURITY VALVE OPENS AT: bar 6,5 6,5 6,5 6,5 6,5 6,5 6,5 6,5 6,5 6,5 6,5 MOTOR PROTECTION IP 55 55 55 55 55 55 55 55 55 55 55