DAX 3F-IR

The DAX 3F-I detector was designed to continuously measure the presence of various explosive gases in the air.
Its measurement principle, catalytic combustion, gives it its major benefits:
- very short response time,
- accuracy and reliability of measurements.
By connecting it to a Dalemans unit, you will obtain a very high performance installation.
ATEX certified and with a stainless steel casing, this detector is especially suitable for applications in aggressive environments or environments where hygiene is essential.

MODEL DAX 3F-I
SENSING HEAD Stainless steel 1,4404 (AISI 316L)
SINTERED METAL FILTER
JUNCTION BOX
CABLE GLAND Nickel plated brass or stainless steel
DIMENSION / WEIGHT 166 x 152,5 x 75 mm / 1.140 g
SENSOR TYPE / SIGNAL Catalytic (Pellistor) / 3-wire mV (bridge Wheatstone)
MEASURING RANGE 0 - 100 % LEL
RESOLUTION

± 3 % of measuring range < 60 % LEL

± 5 % of measuring range > 60 % LEL

RESPONSE TIME (T90) < 30 sec.
EXPECTED OPERATING LIFE > 2 years
SENSOR CHARACTERISTICS* DAL17
SUPPLY VOLTAGE 2,00 V
SUPPLY CURRENT 175 mA ± 20 mA
POWER CONSUMPTION 0,4 W
STORAGE TEMPERATURE -40 ºC to +80 ºC
OPERATING
TEMPERATURE

-20 ºC to +55 ºC for T6 temperature class

-20 ºC to +70 ºC for T5 and T4 temperature class

AMBIENT HUMIDITY 20 - 90 % HR
INTERMITTENT HUMIDITY 10 - 99 % HR
PRESSURE 90 - 110 kPa
CABLE CROSS SECTIONAL
AREA
1,5 - 2,5 mm2 (solid wires)
MAX. CABLE LENGTH Refer to the installation instructions of the control unit
INGRESS PROTECTION IP6X (dust tight)
CABLE ENTRIES 1 x M20 or M25 / 6 - 12 mm (other sizes available)
HAZARDOUS AREA Zones 1 or 2 (gas) - Zones 21 or 22 (dust)
EQUIPMENT GAS GROUPING IIC (methane, propane, ethylene, hydrogen, acetylene)
STANDARDS

EN 60079-0:2006, EN 60079-1:2007, EN 60079-7:2007

EN 61241-0:2006, EN 61241-1:2004

APPROVAL

II 2G Ex d e IIC T6-T4

II 2D Ex tD A21 IP6X Tx ºC

AMBIENT TEMPERATURE

Tamb = -20 ºC to +55 ºC for T6 and T85 ºC

Tamb = -20 ºC to +75 ºC for T5 and T100 ºC

Tamb = -20 ºC to +90 ºC for T4 and T135 ºC

CERTIFICATE FTZU 10 ATEX 0034X