07. GPS-GE
OIL TRANSFER SUCTION UNITS- GE Twin
GE: 2 pumps
Applications & Specific Features
- Oil supply to appliance by gravity feed, GPS unit must be higher than appliance(s).
- Various GPS models available with different sizes of reservoir.
- Standard unit has 2 outlets for 2 appliances, more outlet versions available to special order.
- Suction lift 9m vertical or 200m horizontal. See performance curves (Datasheet).
- Oil supply installations using ‘dead leg’ pipework. GPS unit does not need external controls.
- Anti siphon valve or ‘normally closed’ solenoid valve required at the main oil tank when oil level in tank is above GPS level.
- Special GPS models available with greater reservoir, for acting as power generator reservoir
- Special GPS models available with larger flow, for high output or modulating burners
Technical Characteristics
- Voltage free general alarm outlet.
- Output to attach anti-siphon solenoid valve.
- Oil leak collector tray with infrared detector.
- Safety thermostat (40ºC) for temperature gasification.
- Suction pipe couplings for two burners and one for returns.
Accessories and adaptations
- 8 free relay outputs outlets
MODEL | GPS-35 N | GPS-70 N | GPS-130 N | GPS-200 N | GPS-350 N | GPS-950 N | GPS-1500 N | |
---|---|---|---|---|---|---|---|---|
FLOW | l/h | 30 | 70 | 130 | 200 | 350 | 950 | 1500 |
POWER SUPPLY | VOLTS | 230/400 mono phase | 230/400 tri-phase (*) | 230/400 tri-phase (*) | 230/400 tri-phase (*) | 230/400 tri-phase (*) | 230/400 tri-phase | 230/400 tri-phase |
RECOMMENDED SUCTION PIPE | MM Ø (OD) | 12 | 15 | 15 | 18 | 22 | 25 | 32 |
MOTOR POWER | C.V. | 1/6 | 1/4 | 1/3 | 1/3 | 1/3 | 3/4 | 1½ |
KW | 0,12 | 0,18 | 0,25 | 0,25 | 0,25 | 0,55 | 0,75 | |
SUCTION | BSP THREAD | G 3/8”F | G ½”F | G ½”F | G ¾”F | G ¾”F | G 1”F | G 1 ¼” F |
RETURN PIPE BURNER | BSP THREAD | G 3/8”F | G ½”F | G ½”F | G ½”F | G ¾”F | G ¾”F | G ¾”F |
TANK CAPACITY | lts. | 24 | 68 | 68 | 68 | 238 | 238 | 245 |
MOTOR PROTECTION | IP | 20 | 55 | 55 | 55 | 55 | 55 | 55 |